AGRO

EMC Combination Conduit Glands

Progress Kombi EMC

AGRO Combination EMC conduit glands are an ideal solution if you want to introduce cables inside a conduit into an enclosure and at the same time want a secure, seal and add strain relief for the cables inside, while maitaining EMC immunity

 

The integrated cable gland achieves excellent sealing (IP 68) inside the conduit. This ensure the enclosure stay free from water and condensation ingress.

 

Special version for copper braids, suitable for Flexa ROHRflex.

 

For railway applications where cables are laid in conduits in order to protect them from impacts or manipulation – the same requirements apply as for cable glands: the combination conduit glands must be equipped with a sealing insert made of special TPE according to the requirements of EN 45545.

 

These are available on request and the part number is just prefixed by a capital 'F'.

 

Read more
  • EMC Conduit glands
  • Copper braid versions for ROHRflex corrugated conduit
  • Rail approved versions to EN 45545
  • IP68
1710.80.20.110.1.tif

Eplan-logo.png

To view Agro cable glands via ePlan see the link under 'downloadable resources' further down the page.

1165.84.20.15.tif

Selected variant

Available in several variants

Selected variant

Technical data

General Data

Cable diameter min 4,5 mm
Thread Size (G) M12
Cable diameter max 6 mm
IP class Cable gland IP 68
Insert Type One-Piece

Dimensions

Thread pitch 1,5
Height (H) 35 mm
Spanner width (AF) 17 mm
Thread length 10 mm
Conduit diameter (AD) 10 mm

Materials

Material Nickel-plated brass

*Invisible Heading*

Materials O-ring NBR
Material of seals TPE
Temperature range -40°C ... +100°C

Approvals

Strain relief Version A acc. to EN 62444
Approvals SEV, CE, DNV, EAC, VDE

Additional Data

Pack size 25  
Country of origin CH
Tariff code 74199949
Additional features Max. clamping range depends on conduit inner diameter
Weight 30,2 g

Measurements and connections

Technical illustrations

1165.84.20_Illustration.tif

Copper braided conduit

Querschnitt_Schlauchverschraubung.tif

Combination Coduit gland with integrated cable gland

Product description

AGRO Combination EMC conduit glands are an ideal solution if you want to introduce cables inside a conduit into an enclosure and at the same time want a secure, seal and add strain relief for the cables inside, while maitaining EMC immunity

 

The integrated cable gland achieves excellent sealing (IP 68) inside the conduit. This ensure the enclosure stay free from water and condensation ingress.

 

Special version for copper braids, suitable for Flexa ROHRflex.

 

For railway applications where cables are laid in conduits in order to protect them from impacts or manipulation – the same requirements apply as for cable glands: the combination conduit glands must be equipped with a sealing insert made of special TPE according to the requirements of EN 45545.

 

These are available on request and the part number is just prefixed by a capital 'F'.

 

Accessories

Related

contaclip kds sr90
Product news

Every angle covered with 90 degree cable entry system

Engineers and technicians are seeking solutions that streamline assembly whilst maintaining high levels of protection and flexibility. KDS-SR90 angled screw frames and inlays bring a new level of efficiency to cable routing with a unique 90° entry design.

crouzet millenium slim on limited time discount
Product news

The smallest logic controller ever on limited time discount

The smallest logic controller by Crouzet is now 20% off for a limited time only! A powerhouse packed into just 17.5mm! Efficiency, adaptability, and seamless integration with free software.

11 questions to get the right signalling device with Auer Signal & OEM Automatic
Blog

11 questions to get the right signalling device – a whitepaper

Do you require signalling devices and beacons in your production process? Download our latest whitepaper!

bespoke solutions electricity meter control boxes
Case studies

Control Box Assembly for Industrial Electricity Metering - A case study

Here, our customer requires control boxes for electricity metering systems. We leveraged our expertise to deliver easy-to-install, ready-to-use assemblies. We look forward to creating more of these bespoke control boxes for our customer.

DC circuit protection PISA M and circuit breakers
Blog

Safeguard systems with DC circuit protection

This blog talks all things DC circuit protection including the key components: electronic circuit breakers, fuses and current monitoring devices. As well as how to choose the right protection.

IATECH, the industrial automation technology exhibition OEM automatic
Company news

Recap of IATECH

Did you get a chance to visit IATECH at The Leicester Marriott Hotel? We had over 33 exhibitors and 8 fantastic Tech Talks throughout the day, Read all about the day, here.

Parts Cable diameter min Thread Size (G) Cable diameter max IP class Thread pitch Height (H) Spanner width (AF) Thread length Conduit diameter (AD) Material of seals Temperature range Contact sleeve material Strain relief Approvals Pack size Additional features Weight Price
4,5 mm
M12
6 mm
Cable gland IP 68
1,5
35 mm
17 mm
10 mm
10 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
30,2 g
4,5 mm
M12
6 mm
Cable gland IP 68
1,5
35 mm
19 mm
10 mm
1/4"
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
50,72 g
6 mm
M16
8 mm
Cable gland IP 68
1,5
40 mm
21 mm
10 mm
14 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
55,3 g
6 mm
M16
8 mm
Cable gland IP 68
1,5
38 mm
21 mm
10 mm
5/16"
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
61,4 g
8 mm
M16
10 mm
Cable gland IP 68
1,5
40 mm
21 mm
10 mm
14 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
58,16 g
8 mm
M16
10 mm
Cable gland IP 68
1,5
38 mm
21 mm
10 mm
5/16"
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
57,3 g
8 mm
M20
11 mm
Cable gland IP 68
1,5
42 mm
25 mm
10 mm
17 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
73,6 g
8 mm
M20
11 mm
Cable gland IP 68
1,5
43 mm
27 mm
10 mm
19 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
93,28 g
8 mm
M20
11 mm
Cable gland IP 68
1,5
42 mm
27 mm
10 mm
3/8"
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
100,8 g
8 mm
M20
11 mm
Cable gland IP 68
1,5
38 mm
29 mm
10 mm
1/2"
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
103,6 g
11 mm
M20
14 mm
Cable gland IP 68
1,5
42 mm
25 mm
10 mm
17 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
73,44 g
11 mm
M20
14 mm
Cable gland IP 68
1,5
43 mm
27 mm
10 mm
19 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
90,56 g
11 mm
M20
14 mm
Cable gland IP 68
1,5
38 mm
29 mm
10 mm
1/2"
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
100,36 g
13 mm
M25
16 mm
Cable gland IP 68
1,5
48 mm
29 mm
11 mm
21 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
111 g
13 mm
M25
16 mm
Cable gland IP 68
1,5
52 mm
36 mm
11 mm
3/4"
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
114,6 g
16 mm
M25
19 mm
Cable gland IP 68
1,5
52 mm
36 mm
11 mm
27 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
182,88 g
16 mm
M25
19 mm
Cable gland IP 68
1,5
52 mm
36 mm
11 mm
3/4"
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
25  
Max. clamping range depends on conduit inner diameter
183,6 g
18 mm
M32
21 mm
Cable gland IP 68
1,5
55 mm
36 mm
13 mm
27 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
10  
Max. clamping range depends on conduit inner diameter
188 g
18 mm
M32
21 mm
Cable gland IP 68
1,5
55 mm
45 mm
13 mm
1"
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
10  
Max. clamping range depends on conduit inner diameter
189 g
21 mm
M32
25 mm
Cable gland IP 68
1,5
55 mm
36 mm
13 mm
27 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
10  
Max. clamping range depends on conduit inner diameter
184 g
21 mm
M32
25 mm
Cable gland IP 68
1,5
55 mm
45 mm
13 mm
1"
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
10  
Max. clamping range depends on conduit inner diameter
299,8 g
24 mm
M40
28,5 mm
Cable gland IP 68
1,5
60 mm
46 mm
13 mm
36 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
10  
Max. clamping range depends on conduit inner diameter
287,8 g
24 mm
M40
28,5 mm
Cable gland IP 68
1,5
62 mm
54 mm
13 mm
1 1/4"
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
10  
Max. clamping range depends on conduit inner diameter
580 g
28,5 mm
M40
32 mm
Cable gland IP 68
1,5
60 mm
46 mm
13 mm
36 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
10  
Max. clamping range depends on conduit inner diameter
575,5 g
28,5 mm
M40
32 mm
Cable gland IP 68
1,5
62 mm
54 mm
13 mm
1 1/4"
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
10  
Max. clamping range depends on conduit inner diameter
574,5 g
33 mm
M50
37 mm
Cable gland IP 68
1,5
62 mm
55 mm
14 mm
45 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
5  
Max. clamping range depends on conduit inner diameter
385,8 g
37 mm
M50
41 mm
Cable gland IP 68
1,5
62 mm
55 mm
14 mm
45 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
5  
Max. clamping range depends on conduit inner diameter
597 g
40 mm
M63
46 mm
Cable gland IP 68
1,5
69 mm
70 mm
14 mm
56 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
5  
Max. clamping range depends on conduit inner diameter
680 g
40 mm
M63
46 mm
Cable gland IP 68
1,5
74 mm
70 mm
14 mm
2"
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
5  
Max. clamping range depends on conduit inner diameter
683 g
46 mm
M63
50 mm
Cable gland IP 68
1,5
69 mm
70 mm
14 mm
56 mm
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
5  
Max. clamping range depends on conduit inner diameter
683 g
46 mm
M63
50 mm
Cable gland IP 68
1,5
74 mm
70 mm
14 mm
2"
TPE
-40°C ... +100°C
Version A acc. to EN 62444
SEV, CE, DNV, EAC, VDE
5  
Max. clamping range depends on conduit inner diameter
721,4 g
2,5 mm
M20
10 mm
IP 68 (together with ROHRflex® corrugated tube)
1,5
34,5 mm
24 mm
10 mm
-40°C ... +120°C
Nickel-plated brass
25  
78,4 g
5 mm
M25
16 mm
IP 68 (together with ROHRflex® corrugated tube)
1,5
35,5 mm
30 mm
11 mm
-40°C ... +120°C
Nickel-plated brass
25  
123,96 g
12 mm
M32
20 mm
IP 68 (together with ROHRflex® corrugated tube)
1,5
36,5 mm
36 mm
13 mm
-40°C ... +120°C
Nickel-plated brass
25  
146,6 g
16 mm
M40
27 mm
IP 68 (together with ROHRflex® corrugated tube)
1,5
45 mm
46 mm
13 mm
-40°C ... +120°C
Nickel-plated brass
10  
333,5 g
20 mm
M50
35 mm
IP 68 (together with ROHRflex® corrugated tube)
1,5
46 mm
55 mm
14 mm
-40°C ... +120°C
Nickel-plated brass
5  
435 g
25 mm
M63
45 mm
IP 68 (together with ROHRflex® corrugated tube)
1,5
49 mm
70 mm
14 mm
-40°C ... +120°C
Nickel-plated brass
5  
728 g
4,5 mm
PG 7
6 mm
Cable gland IP 68
35 mm
17 mm
10 mm
10 mm
TPE
-40°C ... +100°C
EAC
25  
Max. clamping range depends on conduit inner diameter
48,84 g
6 mm
PG 9
8 mm
Cable gland IP 68
40 mm
21 mm
10 mm
14 mm
TPE
-40°C ... +100°C
EAC
25  
Max. clamping range depends on conduit inner diameter
53,16 g
8 mm
PG 9
10 mm
Cable gland IP 68
40 mm
21 mm
10 mm
14 mm
TPE
-40°C ... +100°C
EAC
25  
Max. clamping range depends on conduit inner diameter
55,98 g
5,5 mm
PG 11
8,5 mm
Cable gland IP 68
41 mm
25 mm
10 mm
17 mm
TPE
-40°C ... +100°C
EAC
25  
Max. clamping range depends on conduit inner diameter
87,08 g
8,5 mm
PG 11
12 mm
Cable gland IP 68
41 mm
25 mm
10 mm
17 mm
TPE
-40°C ... +100°C
EAC
25  
Max. clamping range depends on conduit inner diameter
81,6 g
8 mm
PG 13
11 mm
Cable gland IP 68
42 mm
27 mm
10 mm
19 mm
TPE
-40°C ... +100°C
EAC
25  
Max. clamping range depends on conduit inner diameter
93,82 g
11 mm
PG 13
14 mm
Cable gland IP 68
42 mm
27 mm
10 mm
19 mm
TPE
-40°C ... +100°C
EAC
25  
Max. clamping range depends on conduit inner diameter
95,12 g
8 mm
PG 16
11 mm
Cable gland IP 68
43 mm
29 mm
10 mm
21 mm
TPE
-40°C ... +100°C
EAC
25  
Max. clamping range depends on conduit inner diameter
111,36 g
11 mm
PG 16
14 mm
Cable gland IP 68
43 mm
29 mm
10 mm
21 mm
TPE
-40°C ... +100°C
EAC
25  
Max. clamping range depends on conduit inner diameter
112,36 g
13 mm
PG 21
16 mm
Cable gland IP 68
55 mm
36 mm
12 mm
27 mm
TPE
-40°C ... +100°C
EAC
10  
Max. clamping range depends on conduit inner diameter
204 g
16 mm
PG 21
19 mm
Cable gland IP 68
55 mm
36 mm
12 mm
27 mm
TPE
-40°C ... +100°C
EAC
10  
Max. clamping range depends on conduit inner diameter
198 g
19 mm
PG 29
23 mm
Cable gland IP 68
57 mm
45 mm
12 mm
36 mm
TPE
-40°C ... +100°C
EAC
10  
Max. clamping range depends on conduit inner diameter
328 g
23 mm
PG 29
25,5 mm
Cable gland IP 68
57 mm
45 mm
12 mm
36 mm
TPE
-40°C ... +100°C
EAC
10  
Max. clamping range depends on conduit inner diameter
328 g
25 mm
PG 36
30,5 mm
Cable gland IP 68
62 mm
54 mm
15 mm
45 mm
TPE
-40°C ... +100°C
EAC
5  
Max. clamping range depends on conduit inner diameter
487 g
30,5 mm
PG 36
35 mm
Cable gland IP 68
62 mm
54 mm
15 mm
45 mm
TPE
-40°C ... +100°C
EAC
5  
Max. clamping range depends on conduit inner diameter
482 g
33 mm
PG 42
37 mm
Cable gland IP 68
62 mm
55 mm
15 mm
45 mm
TPE
-40°C ... +100°C
EAC
5  
Max. clamping range depends on conduit inner diameter
637 g
37 mm
PG 42
41 mm
Cable gland IP 68
62 mm
55 mm
15 mm
45 mm
TPE
-40°C ... +100°C
EAC
5  
Max. clamping range depends on conduit inner diameter
629 g
39 mm
PG 48
43 mm
Cable gland IP 68
69 mm
66 mm
15 mm
56 mm
TPE
-40°C ... +100°C
EAC
5  
Max. clamping range depends on conduit inner diameter
654 g
43 mm
PG 48
46,5 mm
Cable gland IP 68
69 mm
66 mm
15 mm
56 mm
TPE
-40°C ... +100°C
EAC
5  
Max. clamping range depends on conduit inner diameter
649 g

Selected variant

Select a variant in the list

Contact us
If you need any help, you can contact us in one of the following ways:
0116 284 9900
Send e-mail
Use live chat
Do you need help?
Logo

Cookie settings for OEM.CO.UK

Cookies help us improve your experience with us, so in order to be able to handle login information, offer you personalised content and for basic functionality of this website, we use some cookies.

We will never sell on any information about you. 

You can accept all cookies or personalise your cookies preferences, you can also change your cookie preferences at any time by visiting our contact page.

Necessary Cookies

These cookies are necessary for the website to work and can not be turned off in our systems. They are usually used only in response to actions you have taken in connection with a service request, for example when setting personal preferences, logging in or filling out a form.

Analysis and measurement cookies

These cookies allow us to count the number of visits and traffic sources so that we can measure and improve our website performance. They help us know which pages are more or less popular and how visitors navigate around the site. The information that these cookies collect is aggregated and therefore completely anonymous. If you do not allow these cookies, we do not know when you have visited our website.

Marketing cookies

These cookies can be added by our partners. They can use them to create a profile of you, based on your interests, to show you more relevant information. They do not store any personal information - only information about your browser and device. If you do not accept these cookies, you will have a more general and less customized user experience.