Input Data |
|
---|---|
Input current max | 6 A |
Operating voltage dc min | 10 V |
Operating voltage dc max | 30 V |
Power through distribution beam max | 40 A |
Output Data |
|
Selectable current ranges | 1-6A, adjustable in 1A steps |
Output current max | 6 A |
Adjustable current min | 1 A |
Adjustable current max | 6 A |
Adjustable steps | 1 A |
Output semiconductors | Mosfet |
Status indication | LED. Steady green - OK, flashing green - load over 90%, flashing red - fuse triggered, steady red - fuse off |
Voltage drop over semiconductor | 102 mV |
Capacitance max | 10000 µF |
Reaction time | 800 ms |
Dimensions |
|
Width | 8,1 mm |
*Invisible Heading* |
|
---|---|
Depth | 116 mm |
Height | 114,5 mm |
Connection Data |
|
Connection type | Spring 0.25-2.5mm² |
Cross section min | 0,25 mm² |
Cross section max | 2,5 mm² |
IP class | IP20 |
Mounting | DIN-rail |
Approvals |
|
Approvals | CE, cULus |
EMC | EN61000-6-2, EN61000-6-3 |
Additional data |
|
Memory at power failure | Yes, status retained when voltage is back on |
Temperature operational min | -25 °C |
Temperature operational max | 50 °C |
Weight | 120 g |
Engineers and technicians are seeking solutions that streamline assembly whilst maintaining high levels of protection and flexibility. KDS-SR90 angled screw frames and inlays bring a new level of efficiency to cable routing with a unique 90° entry design.
The smallest logic controller by Crouzet is now 20% off for a limited time only! A powerhouse packed into just 17.5mm! Efficiency, adaptability, and seamless integration with free software.
Do you require signalling devices and beacons in your production process? Download our latest whitepaper!
Here, our customer requires control boxes for electricity metering systems. We leveraged our expertise to deliver easy-to-install, ready-to-use assemblies. We look forward to creating more of these bespoke control boxes for our customer.
This blog talks all things DC circuit protection including the key components: electronic circuit breakers, fuses and current monitoring devices. As well as how to choose the right protection.
Did you get a chance to visit IATECH at The Leicester Marriott Hotel? We had over 33 exhibitors and 8 fantastic Tech Talks throughout the day, Read all about the day, here.