LÜTZE
LÜTZE LOCC-Box load monitor offers protection, monitoring and analysis of DC 48V load circuits. Overloads and short-circuits are quickly recognised and the respective circuit is shut down. The error is saved and is therefore already known when switched on again. The current range of the new LÜTZE load monitor is set via a switch from 1 to maximum 6A in steps of 1A. In terms of the characteristic, it is possible to select between five different modes: fast, medium, time-lag, time-lag_1, time-lag_2 to time-lag_3. LEDs indicate 'operation' and 'malfunction' and also the status of the circuit with '90% load' or '100% load'.
The detected faults can be issued as single or collective faults. In addition to manual activation and shutdown, remote switching is also possible. All settings on the LOCC-Box load monitor can be fixed to prevent manipulation. The LÜTZE load monitor not only satisfies the UL approval 508, but also the standards of the flammability categories UL-94-V0 and NFF I2, F2.
The slim width of just 8.1 mm means very little space is required in the control cabinet even with a multi-channel configuration. The new LÜTZE DC 48V current monitor can be used in telecommunication systems and special machinery applications.
Input Data |
|
---|---|
Input current max | 6 A |
Operating voltage dc min | 39 V |
Operating voltage dc max | 58 V |
Power through distribution beam max | 40 A |
Output Data |
|
Selectable current ranges | 1-6A, adjustable in 1A steps |
Output current max | 6 A |
Adjustable current min | 1 A |
Adjustable current max | 6 A |
Adjustable steps | 1 A |
Output semiconductors | Mosfet |
Status indication | LED. Steady green - OK, flashing green - load over 90%, flashing red - fuse triggered, steady red - fuse off |
Voltage drop over semiconductor | 85 mV |
Capacitance max | 10000 µF |
Dimensions |
|
Width | 8,1 mm |
*Invisible Heading* |
|
---|---|
Depth | 116 mm |
Height | 114,5 mm |
Connection Data |
|
Connection type | Spring 0.25-2.5mm² |
Cross section min | 0,25 mm² |
Cross section max | 2,5 mm² |
IP class | IP20 |
Mounting | DIN-rail |
Approvals |
|
Approvals | CE, cULus, GL |
EMC | EN61000-6-2, EN61000-6-3 |
Additional data |
|
Memory at power failure | Yes, status retained when voltage is back on |
Temperature operational min | -25 °C |
Temperature operational max | 50 °C |
Weight | 120 g |
LÜTZE LOCC-Box load monitor offers protection, monitoring and analysis of DC 48V load circuits. Overloads and short-circuits are quickly recognised and the respective circuit is shut down. The error is saved and is therefore already known when switched on again. The current range of the new LÜTZE load monitor is set via a switch from 1 to maximum 6A in steps of 1A. In terms of the characteristic, it is possible to select between five different modes: fast, medium, time-lag, time-lag_1, time-lag_2 to time-lag_3. LEDs indicate 'operation' and 'malfunction' and also the status of the circuit with '90% load' or '100% load'.
The detected faults can be issued as single or collective faults. In addition to manual activation and shutdown, remote switching is also possible. All settings on the LOCC-Box load monitor can be fixed to prevent manipulation. The LÜTZE load monitor not only satisfies the UL approval 508, but also the standards of the flammability categories UL-94-V0 and NFF I2, F2.
The slim width of just 8.1 mm means very little space is required in the control cabinet even with a multi-channel configuration. The new LÜTZE DC 48V current monitor can be used in telecommunication systems and special machinery applications.
Did you get a chance to visit IATECH at The Leicester Marriott Hotel? We had over 33 exhibitors and 8 fantastic Tech Talks throughout the day, Read all about the day, here.
To help experience the capabilities of Z+F machines first-hand, we provide an in-depth demonstration and workshop. These sessions will show the machines in action and allow you to understand their features and gain valuable insight into their operation and benefits.
We are thrilled to announce the launch of IATECH, THe Industrial Automation Technology expo at Leicester Marriott Hotel on 23rd October. The ultimate platform for showcasing our extensive product range and broad business areas, featuring over 50 leading suppliers under one roof!
The specialist vehicle industry can include automotive and EV, heavy vehicles such as agriculture and rail, and marine. This email takes you through some of the various products we offer for specialist vehicle applications.
This blog post delves into the key components, current trends, and best practices in power distribution, illustrating the significant impact these systems have on our daily operations and long-term energy strategies.
We shine a spotlight on surge protection devices (SPDs), a crucial yet often overlooked component in industrial settings. Every surge of electricity, every fluctuation in voltage, poses a potential threat to your machinery and systems.