Lutze's electronic circuit breaker range is being expanded with the new LOCC-Box-Mini. The LOCC-Box-Mini has an integrated negative connection, which makes it very flexible in tight spaces. It has a capacity of 1-8A(1A intervals) and 5 selectable characteristics: Fast (1), Medium (2), slow 1 (3), slow 2 (4), slow 3 (5). It is also adapted for 12/24V DC applications and provides both alarms for tripped fuses with a manual shutdown.
Integrated Negative Connection
The LOCC-Box-Mini has an integrated negative connection which there is a + and - directly on the fuse. This saves both space on the DIN rail and time during installation.
Lutze's Reliable Electronic Circuit Breaker
Lutze offers an electronic circuit breaker for 12 or 24 V DC systems that overcomes issues commonly associated with traditional miniature circuit breakers, particularly over long cable distances and with thin cable cross-sections. Lutze electronic circuit breakers ensure reliable tripping and selectivity without interruptions in unaffected groups. It allows users to adjust the rated current through a thumbwheel under a safety hatch. This adjustment should only be made when the fuse is switched off to prevent electrical hazards.
There are five different characteristics which can be selected to tailor the response to different load conditions, including high inrush currents. Even with the slowest settings the fuse reacts quickly to short circuits compared to a standard miniature circuit breaker.
Adjustable Parameters and Flexible Load Response
For easy connection, the 12 or 24 V DC input can be made directly into each fuse or via a power terminal with a copper rail, which is recommended for installation with multiple fuses mounted close together. A sliding plate mechanism enables easy connection to or isolation from the rail. The circuit breaker can be reset either manually with a button on the front panel or remotely. When a fault occurs, the LED indicator flashes red and when the fault is resolved, it turns solid red. A second reset signal activates the fuse, and the LED lights up green, Also, there is a signal output (open collector) that can be connected to a group providing an alarm in case any fuse in that group trips. The circuit breaker offers a safe system even in the event of electronic failures, thanks to features like a malfunction indicator and internal fuses.
Advanced Features for Safe and Efficient Operation
The signal output from the circuit breaker is an open collector type with a pull-up resistor. It allows for the grouping of fuses and alarms to receive notifications when any fuse in the group trips. The output voltage may vary depending on the external load resistance, Lutze recommends their interface relays for connecting relay coils to the alarm output, ensuring proper function and activation in case of a fault. Additionally, the circuit breaker includes built-in safety features, such as rapid malfunction indicator and an internal fuse to disconnect loads in the event of a short circuit during a fault, ensuring a secure system even during electronic failures.
Input Data |
|
---|---|
Input current max | 8 A |
Operating voltage dc min | 10 V |
Operating voltage dc max | 30 V |
Output Data |
|
Selectable current ranges | 1-10A, adjustable in 1A steps |
Output current max | 8 A |
Adjustable current min | 1 A |
Adjustable current max | 8 A |
Adjustable steps | 1 A |
Output semiconductors | Mosfet |
Status indication | LED. Steady green - OK, flashing green - load over 90%, flashing red - fuse triggered, steady red - fuse off |
Voltage drop over semiconductor | 180 mV |
Capacitance max | 10000 µF |
Reaction time | 800 ms |
Dimensions |
|
Width | 8,1 mm |
*Invisible Heading* |
|
---|---|
Depth | 92 mm |
Height | 87 mm |
Connection Data |
|
Connection type | Spring 0.25-2.5mm² |
Cross section min | 0,25 mm² |
Cross section max | 2,5 mm² |
IP class | IP20 |
Mounting | DIN-rail |
Approvals |
|
Approvals | CE |
EMC | EN61000-6-2, EN61000-6-4 |
Additional data |
|
Memory at power failure | Yes, status retained when voltage is back on |
Temperature operational min | -25 °C |
Temperature operational max | 50 °C |
Weight | 60 g |
Lutze's electronic circuit breaker range is being expanded with the new LOCC-Box-Mini. The LOCC-Box-Mini has an integrated negative connection, which makes it very flexible in tight spaces. It has a capacity of 1-8A(1A intervals) and 5 selectable characteristics: Fast (1), Medium (2), slow 1 (3), slow 2 (4), slow 3 (5). It is also adapted for 12/24V DC applications and provides both alarms for tripped fuses with a manual shutdown.
Integrated Negative Connection
The LOCC-Box-Mini has an integrated negative connection which there is a + and - directly on the fuse. This saves both space on the DIN rail and time during installation.
Lutze's Reliable Electronic Circuit Breaker
Lutze offers an electronic circuit breaker for 12 or 24 V DC systems that overcomes issues commonly associated with traditional miniature circuit breakers, particularly over long cable distances and with thin cable cross-sections. Lutze electronic circuit breakers ensure reliable tripping and selectivity without interruptions in unaffected groups. It allows users to adjust the rated current through a thumbwheel under a safety hatch. This adjustment should only be made when the fuse is switched off to prevent electrical hazards.
There are five different characteristics which can be selected to tailor the response to different load conditions, including high inrush currents. Even with the slowest settings the fuse reacts quickly to short circuits compared to a standard miniature circuit breaker.
Adjustable Parameters and Flexible Load Response
For easy connection, the 12 or 24 V DC input can be made directly into each fuse or via a power terminal with a copper rail, which is recommended for installation with multiple fuses mounted close together. A sliding plate mechanism enables easy connection to or isolation from the rail. The circuit breaker can be reset either manually with a button on the front panel or remotely. When a fault occurs, the LED indicator flashes red and when the fault is resolved, it turns solid red. A second reset signal activates the fuse, and the LED lights up green, Also, there is a signal output (open collector) that can be connected to a group providing an alarm in case any fuse in that group trips. The circuit breaker offers a safe system even in the event of electronic failures, thanks to features like a malfunction indicator and internal fuses.
Advanced Features for Safe and Efficient Operation
The signal output from the circuit breaker is an open collector type with a pull-up resistor. It allows for the grouping of fuses and alarms to receive notifications when any fuse in the group trips. The output voltage may vary depending on the external load resistance, Lutze recommends their interface relays for connecting relay coils to the alarm output, ensuring proper function and activation in case of a fault. Additionally, the circuit breaker includes built-in safety features, such as rapid malfunction indicator and an internal fuse to disconnect loads in the event of a short circuit during a fault, ensuring a secure system even during electronic failures.
Did you get a chance to visit IATECH at The Leicester Marriott Hotel? We had over 33 exhibitors and 8 fantastic Tech Talks throughout the day, Read all about the day, here.
To help experience the capabilities of Z+F machines first-hand, we provide an in-depth demonstration and workshop. These sessions will show the machines in action and allow you to understand their features and gain valuable insight into their operation and benefits.
We are thrilled to announce the launch of IATECH, THe Industrial Automation Technology expo at Leicester Marriott Hotel on 23rd October. The ultimate platform for showcasing our extensive product range and broad business areas, featuring over 50 leading suppliers under one roof!
The specialist vehicle industry can include automotive and EV, heavy vehicles such as agriculture and rail, and marine. This email takes you through some of the various products we offer for specialist vehicle applications.
This blog post delves into the key components, current trends, and best practices in power distribution, illustrating the significant impact these systems have on our daily operations and long-term energy strategies.
We shine a spotlight on surge protection devices (SPDs), a crucial yet often overlooked component in industrial settings. Every surge of electricity, every fluctuation in voltage, poses a potential threat to your machinery and systems.