TEKNOMEGA
The 4 pole disttribution blocks are brass conductors which have galvanized steel screws included this enables insulation between phases.
Â
Each block has a front removable protection screen. Wtih self-extinguishing insulating structure :
Â
 UL 94-V0 approved
Â
Quick hook-up on DIN rails.
Â
Compliant with standards IEC 947-7-1.
Â
Advantages
General Data |
|
---|---|
Rated current | 160 A |
IP class | IP20 |
Nominal insulation voltage | 600 V |
Short-circuit current resistance IPK (peak value) | 22 kA |
Short-circuit current resistance ICW over 1s | 9 kA |
Connection Data |
|
Connections | 12 |
Number of inputs A | 1 |
Input A: diameter | 12 mm |
Input A: wire cross-section stranded, min. | 10 mm² |
Input A: wire cross-section stranded, max. | 50 mm² |
Input A: wire cross-section with wire-end ferrules, min. | 10 mm² |
Input A: wire cross-section with wire-end ferrules, max. | 50 mm² |
Input A: torque, min. | 8 Nm |
Input A: torque, max. | 10 Nm |
Number of outputs A | 3 |
Output A: diameter | 8,5 mm |
Output A: wire cross-section stranded, min. | 10 mm² |
Output A: wire cross-section stranded, max. | 35 mm² |
Output A: wire cross-section stranded with wire-end ferrules, min. | 10 mm² |
*Invisible Heading* |
|
---|---|
Output A: wire cross-section stranded with wire-end ferrules, max. | 25 mm² |
Output A: torque, min. | 2 Nm |
Output A: torque, max. | 3 Nm |
Number of outputs B | 8 |
Output B: diameter | 7 mm |
Output B: wire cross-section stranded, min. | 2,5 mm² |
Output B: wire cross-section stranded, max. | 16 mm² |
Output B: wire cross-section stranded with wire-end ferrules, min. | 1,5 mm² |
Output B: wire cross-section stranded with wire-end ferrules, max. | 16 mm² |
Output B: torque, min. | 2 Nm |
Output B: torque, max. | 3 Nm |
Screw type | Galvanized steel screws |
Dimensions |
|
Fix. Hole space | 135 mm |
Length (L) | 154 mm |
Height (H) | 95 mm |
Width (P) | 67 mm |
Additional Data |
|
Pack size | 1 |
The 4 pole disttribution blocks are brass conductors which have galvanized steel screws included this enables insulation between phases.
Â
Each block has a front removable protection screen. Wtih self-extinguishing insulating structure :
Â
 UL 94-V0 approved
Â
Quick hook-up on DIN rails.
Â
Compliant with standards IEC 947-7-1.
Â
Advantages
|
|
|
|
|
||
---|---|---|---|---|---|---|
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
Parts | Connections | Number of inputs A | Input A: diameter | Input A: wire cross-section stranded, min. | Input A: wire cross-section stranded, max. | Input A: wire cross-section with wire-end ferrules, min. | Input A: wire cross-section with wire-end ferrules, max. | Input A: torque, min. | Input A: torque, max. | Number of outputs A | Output A: wire cross-section stranded with wire-end ferrules, max. | Number of outputs B | Fix. Hole space | Length (L) | Height (H) | Width (P) | Width (I) | Price | ||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
4 pole Distribution Block 160 A - RPQ 160-11
Art:
RPQ1015
Copied
|
12
|
1
|
11,5 mm
|
10 mm²
|
50 mm²
|
10 mm²
|
50 mm²
|
8 Nm
|
10 Nm
|
3
|
25 mm²
|
8
|
150 mm
|
168 mm
|
85 mm
|
70 mm
|
|
| ||
Up & Down: connection of 2 phases on each side - RPQ 160-11-U&D
Art:
RPQ1016
Copied
|
12
|
1
|
11,5 mm
|
10 mm²
|
50 mm²
|
10 mm²
|
50 mm²
|
8 Nm
|
10 Nm
|
3
|
16 mm²
|
8
|
163 mm
|
176 mm
|
105 mm
|
55 mm
|
|
| ||
4 pole 160 A with modular exits - RPQ 160-11M
Art:
RPQ1017
Copied
|
12
|
1
|
11,5 mm
|
10 mm²
|
50 mm²
|
10 mm²
|
50 mm²
|
8 Nm
|
10 Nm
|
3
|
16 mm²
|
8
|
163 mm
|
176 mm
|
105 mm
|
55 mm
|
|
| ||
Inputs orthogonal to outputs - RPQ160-11-SI
Art:
RPQ1018
Copied
|
12
|
1
|
12 mm
|
10 mm²
|
50 mm²
|
10 mm²
|
50 mm²
|
8 Nm
|
10 Nm
|
3
|
25 mm²
|
8
|
135 mm
|
154 mm
|
95 mm
|
67 mm
|
|
| ||
Specific tool for RPQ1017 - RPN160-14
Art:
RPQ2017
Copied
|
14
|
|
|
|
|
|
|
|
|
4
|
16 mm²
|
10
|
|
161 mm
|
27 mm
|
17 mm
|
57 mm
|
|
Select a variant in the list
If you need any help, you can contact us in one of the following ways: