Puls Dimension C-series stands for cost optimization without compromising quality, reliability or performance.

CP10.241 is the second generation C-series 1-phase 10 A that sets new records by using the latest technology and sophisticated thermal design. With an efficiency of 95%, the power losses are very small and thus the width is reduced down to 39 mm. The efficiency is also very high at lower loads which is the normal operating condition. The mean value is on the whole 94.3% at 230 V ac. No-load loss is only 1.8 W.

Power boost of 20% enables higher current extraction without voltage drops. This is especially useful during start-ups and to bridge the current peaks in the application. The power reserve can be used continuously up to + 45°C and short periods from +45 to +60°C.

Short-circuit currents. CP10 can provide short circuit current which is 3 times the nominal current for at least 12 ms, which helps secondary fuses and achieve selectivity. For more information see under Sec, fuses.

Hiccup Plus.
With Pulse new short circuit technology ensures optimum protection. The unit leaves a very high short circuit that solves secondary fuses and provide sufficient starting current for example dc motors. If the output voltage drops below 13 V dc will be 2x the rated current is left for 2 seconds, then close the unit by the end to make a new restart attempts after about 18 seconds. This feature ensures a high short-circuit / overload current while avoiding a constant high current that can lead to thermal problems with cables and component damage.

More technical advantages. CP10 has active power factor correction (PFC) and active inrush current limiter that effectively reduces start currents which are ideal if several units are connected in the same phase or if the supply is current limited through example. AC UPS. The protection is always active, regardless of the temperature. DC-OK output, wide temperature range, a large number of approvals and transient filter which ensures operation in störrik electrical environment makes the unit suitable for virtually all installations.

 
For ventilation, we recommend a clearance of 40 mm over 20 mm below.
We recommend 5 mm air gap to the sides. (15 mm on the sides of adjacent product is a heat source.) 

 

Switching

CP10.241_connection.eps

A:Primary side/control voltage

 

B: Secondary. Output voltage

 

C: Potentiometer adjustable output voltageg 24-28 V dc

 

D: DC-OK LED. Lights when the voltage is 90% of the set value

 

E: DC-OK relay output. Closes when the output voltage is OK

 

Secondary fuses

Breakers is the most common type of fuse for ac voltage but is also used for dc voltages. Power supply always has a current limitation compared with an electricity network which hampers tripping of a circuit breaker of the magnetic field, especially if the voltage is as low as 24 V dc. Greater consideration must be given to the cable diameter and cable lengths. This even if the power supply is able to deliver high short circuit currents. For long cables and / or thin cable area so the solution is electronic fuses. Click on the link for more information.

 

Pulse CT10.241 have high short-circuit currents which enables tripping within 10 ms of length and cross sectional area is included within the specification.

 

 

 

 

 

 

 

 

 

 

 

Save tripping of breakers with different
cable lengths/diameters

Short circuit. Fig 3-2

 

 

 Safe tripping of breakers with different cable lengths/diameters

Output characteristics

 

Hiccup-function. Fig 3-3

Hiccup function

Description of Hiccupplus-function

Thanks to the unique Pulse Hiccupplus ensures a high short circuit current while avoiding the risk of overheated cables and damage to the connected loads. When a short circuit occurs following

1. High peak power that enables tripping in 12 ms Figure 3-2

 

2. The unit leaves the double power for 2 s 21 A

 

3. After 2 seconds the unit shuts off. Then try to restart every 18 seconds. If the fault is removed, the unit starts automatically, otherwise it will lose further 18 s. The operation does not burden the cabling and does not cause damage to the electronics

 

Read more
  • Output 10 A
  • Up to 95.2% efficiency
  • Only 39 mm wide
  • 20% power reserve
  • Hiccup Plus

Selected variant

Available in several variants

Selected variant

Technical data

Input data

Input voltage range Wide-range
Input voltage ac 100-240 V
Input voltage ac min 85 V AC
Input voltage dc max 180 V DC
Input voltage dc 110-150 V
Input voltage ac max 264 V AC
Inrush current at 230 V ac typical 9 A
Number of phases 1
Inrush current at 120 V ac typical 6 A
Power factor at 120 V ac, full load. Typical 0,99
Power factor at 230 V ac, full load. Typical 0,97
Input voltage dc min 88 V DC

Output data

Output voltage min 24 V DC
Output voltage 24 V DC
Output voltage max 28 V DC
Power 240 W
Output current 10 A

Efficiency / Lifetime / MTBF

Lifetime at 120 V ac, full load and +40 ° C 75000 h
MTBF (IEC 61709) 230 V ac, max load, 40 ° C 661000 h
Efficiency at 230 V ac, full load, typical 95,2 %
Efficiency at 230 V ac, typical 94,3 %
Lifetime at 230 V ac, full load and +40 ° C 120000 h
Efficiency at 120 V ac, full load, typical 93,6 %

Dimensions

Weight 0,6 kg
Depth 117 mm
Width 39 mm
Height 124 mm

Other

IP class IP20
Power consumption 120 V ac 2,15 A
Ripple max 50 mV pp
Power drop from +60 °C to + 70 °C 6 W/°C
Relay output 30 V DC / 1 A Resistive Load
Clamp type Screw
Temperature min without derating -25 °C
Hold time at 120 V ac, typical full load 37 ms
Series Dimension C
Hold time at 230 V ac, typical full load 37 ms
Power consumption 230 V ac 1,13 A
Supply frequency 50-60 ±6 %
Approvals ABS, CB, CE, CSA, EX, GL, IECEx, UL
Temperature max without derating 60 °C
Material protection Aluminium
Type Power Supply AC-DC
Active Transient Yes
DC relay output Yes

Product description

Puls Dimension C-series stands for cost optimization without compromising quality, reliability or performance.

CP10.241 is the second generation C-series 1-phase 10 A that sets new records by using the latest technology and sophisticated thermal design. With an efficiency of 95%, the power losses are very small and thus the width is reduced down to 39 mm. The efficiency is also very high at lower loads which is the normal operating condition. The mean value is on the whole 94.3% at 230 V ac. No-load loss is only 1.8 W.

Power boost of 20% enables higher current extraction without voltage drops. This is especially useful during start-ups and to bridge the current peaks in the application. The power reserve can be used continuously up to + 45°C and short periods from +45 to +60°C.

Short-circuit currents. CP10 can provide short circuit current which is 3 times the nominal current for at least 12 ms, which helps secondary fuses and achieve selectivity. For more information see under Sec, fuses.

Hiccup Plus.
With Pulse new short circuit technology ensures optimum protection. The unit leaves a very high short circuit that solves secondary fuses and provide sufficient starting current for example dc motors. If the output voltage drops below 13 V dc will be 2x the rated current is left for 2 seconds, then close the unit by the end to make a new restart attempts after about 18 seconds. This feature ensures a high short-circuit / overload current while avoiding a constant high current that can lead to thermal problems with cables and component damage.

More technical advantages. CP10 has active power factor correction (PFC) and active inrush current limiter that effectively reduces start currents which are ideal if several units are connected in the same phase or if the supply is current limited through example. AC UPS. The protection is always active, regardless of the temperature. DC-OK output, wide temperature range, a large number of approvals and transient filter which ensures operation in störrik electrical environment makes the unit suitable for virtually all installations.

 
For ventilation, we recommend a clearance of 40 mm over 20 mm below.
We recommend 5 mm air gap to the sides. (15 mm on the sides of adjacent product is a heat source.) 

 

Switching

CP10.241_connection.eps

A:Primary side/control voltage

 

B: Secondary. Output voltage

 

C: Potentiometer adjustable output voltageg 24-28 V dc

 

D: DC-OK LED. Lights when the voltage is 90% of the set value

 

E: DC-OK relay output. Closes when the output voltage is OK

 

Secondary fuses

Breakers is the most common type of fuse for ac voltage but is also used for dc voltages. Power supply always has a current limitation compared with an electricity network which hampers tripping of a circuit breaker of the magnetic field, especially if the voltage is as low as 24 V dc. Greater consideration must be given to the cable diameter and cable lengths. This even if the power supply is able to deliver high short circuit currents. For long cables and / or thin cable area so the solution is electronic fuses. Click on the link for more information.

 

Pulse CT10.241 have high short-circuit currents which enables tripping within 10 ms of length and cross sectional area is included within the specification.

 

 

 

 

 

 

 

 

 

 

 

Save tripping of breakers with different
cable lengths/diameters

Short circuit. Fig 3-2

 

 

 Safe tripping of breakers with different cable lengths/diameters

Output characteristics

 

Hiccup-function. Fig 3-3

Hiccup function

Description of Hiccupplus-function

Thanks to the unique Pulse Hiccupplus ensures a high short circuit current while avoiding the risk of overheated cables and damage to the connected loads. When a short circuit occurs following

1. High peak power that enables tripping in 12 ms Figure 3-2

 

2. The unit leaves the double power for 2 s 21 A

 

3. After 2 seconds the unit shuts off. Then try to restart every 18 seconds. If the fault is removed, the unit starts automatically, otherwise it will lose further 18 s. The operation does not burden the cabling and does not cause damage to the electronics

 

Accessories

Related products

Related

contaclip kds sr90
Product news

Every angle covered with 90 degree cable entry system

Engineers and technicians are seeking solutions that streamline assembly whilst maintaining high levels of protection and flexibility. KDS-SR90 angled screw frames and inlays bring a new level of efficiency to cable routing with a unique 90° entry design.

crouzet millenium slim on limited time discount
Product news

The smallest logic controller ever on limited time discount

The smallest logic controller by Crouzet is now 20% off for a limited time only! A powerhouse packed into just 17.5mm! Efficiency, adaptability, and seamless integration with free software.

11 questions to get the right signalling device with Auer Signal & OEM Automatic
Blog

11 questions to get the right signalling device – a whitepaper

Do you require signalling devices and beacons in your production process? Download our latest whitepaper!

bespoke solutions electricity meter control boxes
Case studies

Control Box Assembly for Industrial Electricity Metering - A case study

Here, our customer requires control boxes for electricity metering systems. We leveraged our expertise to deliver easy-to-install, ready-to-use assemblies. We look forward to creating more of these bespoke control boxes for our customer.

DC circuit protection PISA M and circuit breakers
Blog

Safeguard systems with DC circuit protection

This blog talks all things DC circuit protection including the key components: electronic circuit breakers, fuses and current monitoring devices. As well as how to choose the right protection.

IATECH, the industrial automation technology exhibition OEM automatic
Company news

Recap of IATECH

Did you get a chance to visit IATECH at The Leicester Marriott Hotel? We had over 33 exhibitors and 8 fantastic Tech Talks throughout the day, Read all about the day, here.

Parts Input voltage dc max Input voltage dc Relay output Clamp type Approvals Conformal coated Price
180 V DC
110-150 V
30 V DC / 1 A Resistive Load
Screw
ABS, CB, CE, CSA, EX, GL, IECEx, UL
180 V DC
110-150 V
Spring-clamp
ABS, CB, CE, CSA, EX, GL, IECEx, UL
180 V DC
110-150 V
Push in
ATEX, CB, CE, CSA, IECEx, UL
180 V DC
110-150 V
Screw
ABS, CB, CE, CSA, EX, GL, IECEx, UL
Yes
360 V DC
110-300 V
Screw
ABS, CB, CE, CSA, EX, GL, IECEx, UL

Selected variant

Select a variant in the list

Contact us
If you need any help, you can contact us in one of the following ways:
0116 284 9900
Send e-mail
Use live chat
Do you need help?
Logo

Cookie settings for OEM.CO.UK

Cookies help us improve your experience with us, so in order to be able to handle login information, offer you personalised content and for basic functionality of this website, we use some cookies.

We will never sell on any information about you. 

You can accept all cookies or personalise your cookies preferences, you can also change your cookie preferences at any time by visiting our contact page.

Necessary Cookies

These cookies are necessary for the website to work and can not be turned off in our systems. They are usually used only in response to actions you have taken in connection with a service request, for example when setting personal preferences, logging in or filling out a form.

Analysis and measurement cookies

These cookies allow us to count the number of visits and traffic sources so that we can measure and improve our website performance. They help us know which pages are more or less popular and how visitors navigate around the site. The information that these cookies collect is aggregated and therefore completely anonymous. If you do not allow these cookies, we do not know when you have visited our website.

Marketing cookies

These cookies can be added by our partners. They can use them to create a profile of you, based on your interests, to show you more relevant information. They do not store any personal information - only information about your browser and device. If you do not accept these cookies, you will have a more general and less customized user experience.