PULS
Pulse Dimension Q is a series power supply with very high performance. The efficiency is high over a wide load range, which results in reduced power consumption and longer life regardless of load current. An average efficiency is 93.8% with a peak value of 94.6%. The power loss at idle is only 12 W.
The bonus power provides 50% extra reserve with retained 24 V dc (60 A) which is an advantage when connected loads have high starting currents and to bridge temporary current peaks. The bonus power is limited to 4 seconds to avoid constant overloading of the power supply and wiring. In addition to the bonus effect leave the unit a very high short-circuit current (for a number of milliseconds) that helps to secondary fuses. If the overload remains after 4 sec. Ports end in the so called, hiccup mode. When the output voltage drops below 21 V dc shut the unit by the end of the 18's. And then make a new start attempt. If the overload / short connection is gone restarts the power supply automatically. If the overload / short circuit persists, the unit output current of approx. 2 sec and then again turn off.
Heavy transient ensure operation also in very störrik electrical environment and also has QS40.244 active inrush current protection, which means a very low starting current, even if the unit has been in operation for a longer time. Especially useful for redundant / parallel-connected systems.
Simple diagnostics via DC-OK relay that falls on the output voltage deviates more than 10% from the set value, a green LED indicates DC-OK, the red LED indicates overload.
The unit can also be remote controlled for on / off function, three different connection options available. Can be used instead of expensive DC contactors when you need to break up the 24 VDC side. Note. remote control function has no safety circuit and therefore should not be used in the security context.
Active PFC reduces power consumption and harmonics close to zero. Moreover, the current distribution in the phases were much more even at the voltage asymmetry.
Â
Output characteristics | |
Remote function | |
The power supply has bonus power that enables high power extraction with retained 24 V dc for 4 seconds, which is a major advantage when connected loads have high starting currents, for example. engines. How often you can use the bonus effect depends on the application. With the below chart and formula estimated the repeat time available for each individual application. The bonus power is available as soon as the power supply is started and after a short circuit
Â
Bonus power | Work cycle | |
Po | Nominal load current | |
Ppeak | Peak current | |
To | Time between bonus effect | |
Tpeak | Peak current time | |
Work cycle | Tpeak/(Tpeak+To) | |
To= | Tpeak-(duty cycle)*Tpeak)/work cycle | |
Ex. Peak current (Ppeak) 50 A = 125%. Peak time is 3 seconds. Nominal load current (Po) is 30 A. 30 A = 75% of In. According to the diagram, the working cycle about 0.45. To = 3 - (0.45 * 3) / 0.45 = 3.6. Maximum repeat time of bonus power is 3.6 seconds. |
Â
Â
Indicators | Overload | DC-OK | DC-OK |
Normal operation | Off | On | Closed |
During bonus poweroutput | Off | On | Closed |
Overload (Hick-up) | Flashing | Off | Open |
Short circuit | Flashing | Off | Open |
Over temperature | Flashing | Off | Open |
Remote shutdown | Flashing | Off | Open |
No input voltage | Off | Off | Open |
Ex. Peak current (Ppeak) 50 A = 125%. Peak time is 3 seconds. Nominal load current (Po) is 30 A. 30 A = 75% of In. According to the diagram, the working cycle about 0.45. To = 3 - (0.45 * 3) / 0.45 = 3.6. Maximum repeat time of bonus power is 3.6 seconds. |
Â
Input data |
|
---|---|
Input voltage ac | 100-240 V |
Input voltage ac min | 90 V AC |
Input voltage ac max | 264 V AC |
Inrush current at 120 V ac typical | 17 A |
Inrush current at 230 V ac typical | 11 A |
Input voltage range | Wide-range |
Power factor at 120 V ac, full load. Typical | 0,99 |
Power factor at 230 V ac, full load. Typical | 0,99 |
Number of phases | 1 |
Output data |
|
Output voltage | 24 V DC |
Output voltage min | 24 V DC |
Output voltage max | 28 V DC |
Output current | 40 A |
Power | 960 W |
Efficiency / Lifetime / MTBF |
|
Efficiency at 120 V ac, full load, typical | 93,6 % |
Efficiency at 230 V ac, typical | 93,9 % |
Efficiency at 230 V ac, full load, typical | 94,6 % |
Lifetime at 120 V ac, full load and +40 ° C | 64000 h |
Lifetime at 230 V ac, full load and +40 ° C | 84000 h |
MTBF (IEC 61709) 230 V ac, max load, 40 ° C | 300000 h |
Dimensions |
|
Width | 125 mm |
*Invisible Heading* |
|
---|---|
Height | 124 mm |
Depth | 127 mm |
Weight | 1,9 kg |
Other |
|
Approvals | ABS, ATEX, CB, CE, CSA, GL, IECEx, UL |
Hold time at 120 V ac, typical full load | 27 ms |
Hold time at 230 V ac, typical full load | 27 ms |
IP class | IP20 |
Clamp type | Spring-clamp |
Material protection | Aluminium |
Supply frequency | 50-60 Hz +-6% |
Ripple max | 100 mV pp |
Series | Dimension Q |
Power consumption 120 V ac | 8,6 A |
Power consumption 230 V ac | 4,5 A |
Power drop from +60 °C to + 70 °C | 24 W/°C |
Temperature min without derating | -25 °C |
Temperature max without derating | 60 °C |
Type Power Supply | AC-DC |
DC relay output | Yes |
Pulse Dimension Q is a series power supply with very high performance. The efficiency is high over a wide load range, which results in reduced power consumption and longer life regardless of load current. An average efficiency is 93.8% with a peak value of 94.6%. The power loss at idle is only 12 W.
The bonus power provides 50% extra reserve with retained 24 V dc (60 A) which is an advantage when connected loads have high starting currents and to bridge temporary current peaks. The bonus power is limited to 4 seconds to avoid constant overloading of the power supply and wiring. In addition to the bonus effect leave the unit a very high short-circuit current (for a number of milliseconds) that helps to secondary fuses. If the overload remains after 4 sec. Ports end in the so called, hiccup mode. When the output voltage drops below 21 V dc shut the unit by the end of the 18's. And then make a new start attempt. If the overload / short connection is gone restarts the power supply automatically. If the overload / short circuit persists, the unit output current of approx. 2 sec and then again turn off.
Heavy transient ensure operation also in very störrik electrical environment and also has QS40.244 active inrush current protection, which means a very low starting current, even if the unit has been in operation for a longer time. Especially useful for redundant / parallel-connected systems.
Simple diagnostics via DC-OK relay that falls on the output voltage deviates more than 10% from the set value, a green LED indicates DC-OK, the red LED indicates overload.
The unit can also be remote controlled for on / off function, three different connection options available. Can be used instead of expensive DC contactors when you need to break up the 24 VDC side. Note. remote control function has no safety circuit and therefore should not be used in the security context.
Active PFC reduces power consumption and harmonics close to zero. Moreover, the current distribution in the phases were much more even at the voltage asymmetry.
Â
Output characteristics | |
Remote function | |
The power supply has bonus power that enables high power extraction with retained 24 V dc for 4 seconds, which is a major advantage when connected loads have high starting currents, for example. engines. How often you can use the bonus effect depends on the application. With the below chart and formula estimated the repeat time available for each individual application. The bonus power is available as soon as the power supply is started and after a short circuit
Â
Bonus power | Work cycle | |
Po | Nominal load current | |
Ppeak | Peak current | |
To | Time between bonus effect | |
Tpeak | Peak current time | |
Work cycle | Tpeak/(Tpeak+To) | |
To= | Tpeak-(duty cycle)*Tpeak)/work cycle | |
Ex. Peak current (Ppeak) 50 A = 125%. Peak time is 3 seconds. Nominal load current (Po) is 30 A. 30 A = 75% of In. According to the diagram, the working cycle about 0.45. To = 3 - (0.45 * 3) / 0.45 = 3.6. Maximum repeat time of bonus power is 3.6 seconds. |
Â
Â
Indicators | Overload | DC-OK | DC-OK |
Normal operation | Off | On | Closed |
During bonus poweroutput | Off | On | Closed |
Overload (Hick-up) | Flashing | Off | Open |
Short circuit | Flashing | Off | Open |
Over temperature | Flashing | Off | Open |
Remote shutdown | Flashing | Off | Open |
No input voltage | Off | Off | Open |
Ex. Peak current (Ppeak) 50 A = 125%. Peak time is 3 seconds. Nominal load current (Po) is 30 A. 30 A = 75% of In. According to the diagram, the working cycle about 0.45. To = 3 - (0.45 * 3) / 0.45 = 3.6. Maximum repeat time of bonus power is 3.6 seconds. |
Â
Did you get a chance to visit IATECH at The Leicester Marriott Hotel? We had over 33 exhibitors and 8 fantastic Tech Talks throughout the day, Read all about the day, here.
To help experience the capabilities of Z+F machines first-hand, we provide an in-depth demonstration and workshop. These sessions will show the machines in action and allow you to understand their features and gain valuable insight into their operation and benefits.
We are thrilled to announce the launch of IATECH, THe Industrial Automation Technology expo at Leicester Marriott Hotel on 23rd October. The ultimate platform for showcasing our extensive product range and broad business areas, featuring over 50 leading suppliers under one roof!
The specialist vehicle industry can include automotive and EV, heavy vehicles such as agriculture and rail, and marine. This email takes you through some of the various products we offer for specialist vehicle applications.
This blog post delves into the key components, current trends, and best practices in power distribution, illustrating the significant impact these systems have on our daily operations and long-term energy strategies.
We shine a spotlight on surge protection devices (SPDs), a crucial yet often overlooked component in industrial settings. Every surge of electricity, every fluctuation in voltage, poses a potential threat to your machinery and systems.
|
|
|
|
|
||
---|---|---|---|---|---|---|
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
Parts | Input voltage ac | Input voltage ac min | Inrush current at 120 V ac typical | Inrush current at 230 V ac typical | Input voltage range | Power factor at 120 V ac, full load. Typical | Power factor at 230 V ac, full load. Typical | Efficiency at 120 V ac, full load, typical | Efficiency at 230 V ac, typical | Lifetime at 120 V ac, full load and +40 ° C | Lifetime at 230 V ac, full load and +40 ° C | MTBF (IEC 61709) 230 V ac, max load, 40 ° C | Weight | Approvals | Hold time at 120 V ac, typical full load | Hold time at 230 V ac, typical full load | Supply frequency | Power consumption 120 V ac | Power consumption 230 V ac | Price | ||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
PSU 100-240V ac I/P 24V dc 40A 960W O/P
Art:
QS40.241
Copied
|
100-240 V
|
90 V AC
|
17 A
|
11 A
|
Wide-range
|
0,99
|
0,99
|
93,6 %
|
93,9 %
|
64000 h
|
84000 h
|
300000 h
|
1,9 kg
|
ABS, ATEX, CB, CE, CSA, GL, IECEx, UL
|
27 ms
|
27 ms
|
50-60 Hz +-6%
|
8,6 A
|
4,5 A
|
| ||
PSU 200-240V ac I/P 24V dc 40A 960W O/P
Art:
QS40.244
Copied
|
200-240 V
|
170 V AC
|
|
14 A
|
|
|
0,96
|
|
93,8 %
|
|
59000 h
|
366000 h
|
1,8 kg
|
ABS, CB, CE, CSA, GL, UL
|
|
30 ms
|
50-60 ±6 %
|
|
4,6 A
|
|
Select a variant in the list