PULS

Power supply 3-phase, 24 V dc Dimension Q, 40A

Pulse Dimension Q is a series power supply with very high performance and reliability.

QT40.241 have built primary fuses that make it possible to connect the unit without the need for intermediate fuses up to 32 A (UL) which saves space and money. The efficiency is high over a wide load range, which results in reduced power consumption and longer life regardless of load current. An average efficiency is 94.7% with a peak value of 95.3%. The power loss at idle is very low, 9.5 W.

The bonus power provides 50% extra reserve with retained 24 V dc (60 A) which is an advantage when connected loads have high starting currents and to bridge temporary current peaks. The bonus power is limited to 4 seconds to avoid constant overloading of the power supply and wiring. In addition to the bonus effect leave the unit a very high short-circuit current (ms) that helps to secondary fuses. See technical data for example.

Active transient ensure operation also in very störrik electrical environment and also has QT40.241 active inrush current protection, which means a very low starting current, even if the unit has been in operation for a longer time. Especially useful for redundant / parallel-connected systems.

Simple diagnostics via DC-OK relay that falls on the output voltage deviates more than 10% from the set value, a green LED indicates DC-OK, Red LED indicates overload.

The unit can also be remote controlled for on / off function, three different connection options available. See the "Technical data". Can be used instead of expensive DC contactors when you need to break up the 24 V side (NB. The remote control function has no safety circuit and therefore should not be used in the security context).

Active PFC reduces power consumption, harmonics close to zero, in addition, the power distribution in phases much smoother at power asymmetry.

Bonus power

The power supply has bonus power that enables high power extraction with retained 24 V DC for 4 seconds, which is a major advantage when connected loads have high starting currents, such as the case with motors. How often bonus power can be utilised depends on the application. With the following diagram and formula, the repeat time can be calculated for each application. The bonus power is available as soon as the power supply is started and directly after a short circuit.

 

We recommend free space of 40 mm above and 20 mm under the power supply, and 5 mm at the sides.

 

Bonus power

Operating cycle

Bonus effect diagram power supply QT20.241

Duty cycle diagram power supply QT20.241

Po

Nominal load current

Ppeak

Peak current

To

Time between bonus power

Tpeak

Peak current I time

Operating cycle

Tpeak / (Tpeak + To)

To=

Tpeak - (operating cycle * Tpeak) / operating cycle

Example: Peak current (Ppeak) is 50 A =125%. The peak time is 3 seconds. Nominal load current (Po) is 30 A. 30 A =75% of Inom. According to the diagram, the operating cycle is about 0.45. To = 3 - (0.45 * 3) / 0.45 = 3.6. Maximum repeat time of bonus power is 3.6 seconds.

 

 

Output characteristic

188607_555.eps

Remote control function

188604_555.eps

 

Read more
  • Output current of 40 A
  • Up to 95.3% efficiency
  • Remote Function
  • Maximum performance
  • Integrated primary fuses

Selected variant

Available in several variants

Selected variant

Technical data

Input data

Input voltage range Wide-range
Input voltage ac 380-480 V
Input voltage ac min 323 V AC
Input voltage ac max 576 V AC
Inrush current at 400 V ac typical 5 A
Number of phases 3
Power factor at 400 V ac, full load. Typical 0,88

Output data

Output voltage min 24 V DC
Output voltage 24 V DC
Output voltage max 28 V DC
Power 960 W
Output current 40 A

Efficiency / Lifetime / MTBF

MTBF (IEC 61709) 400 V ac, max loan, +40 °C 375000 h
Lifetime at 400 V ac, full load and +40 ° C 69000 h
Efficiency at 400 V ac, full load, typical 95,3 %
Efficiency at 400 V ac, typical 94,7 %

Dimensions

Weight 1,5 kg
Depth 127 mm

*Invisible Heading*

Width 110 mm
Height 124 mm

Other

IP class IP20
Ripple max 100 mV pp
Hold time at 400 V ac, typical full load 25 ms
Power consumption at 400 V ac 1,65 A
Power drop from +60 °C to + 70 °C 24 W/°C
Clamp type Screw on
Temperature min without derating -25 °C
Series Dimension Q
Supply frequency 50-60 ±6 %
Approvals CB, CE, CSA, GL, UL
Temperature max without derating 60 °C
Material protection Aluminium
Type Power Supply AC-DC
Active Transient Yes
DC relay output Yes

Product description

Pulse Dimension Q is a series power supply with very high performance and reliability.

QT40.241 have built primary fuses that make it possible to connect the unit without the need for intermediate fuses up to 32 A (UL) which saves space and money. The efficiency is high over a wide load range, which results in reduced power consumption and longer life regardless of load current. An average efficiency is 94.7% with a peak value of 95.3%. The power loss at idle is very low, 9.5 W.

The bonus power provides 50% extra reserve with retained 24 V dc (60 A) which is an advantage when connected loads have high starting currents and to bridge temporary current peaks. The bonus power is limited to 4 seconds to avoid constant overloading of the power supply and wiring. In addition to the bonus effect leave the unit a very high short-circuit current (ms) that helps to secondary fuses. See technical data for example.

Active transient ensure operation also in very störrik electrical environment and also has QT40.241 active inrush current protection, which means a very low starting current, even if the unit has been in operation for a longer time. Especially useful for redundant / parallel-connected systems.

Simple diagnostics via DC-OK relay that falls on the output voltage deviates more than 10% from the set value, a green LED indicates DC-OK, Red LED indicates overload.

The unit can also be remote controlled for on / off function, three different connection options available. See the "Technical data". Can be used instead of expensive DC contactors when you need to break up the 24 V side (NB. The remote control function has no safety circuit and therefore should not be used in the security context).

Active PFC reduces power consumption, harmonics close to zero, in addition, the power distribution in phases much smoother at power asymmetry.

Bonus power

The power supply has bonus power that enables high power extraction with retained 24 V DC for 4 seconds, which is a major advantage when connected loads have high starting currents, such as the case with motors. How often bonus power can be utilised depends on the application. With the following diagram and formula, the repeat time can be calculated for each application. The bonus power is available as soon as the power supply is started and directly after a short circuit.

 

We recommend free space of 40 mm above and 20 mm under the power supply, and 5 mm at the sides.

 

Bonus power

Operating cycle

Bonus effect diagram power supply QT20.241

Duty cycle diagram power supply QT20.241

Po

Nominal load current

Ppeak

Peak current

To

Time between bonus power

Tpeak

Peak current I time

Operating cycle

Tpeak / (Tpeak + To)

To=

Tpeak - (operating cycle * Tpeak) / operating cycle

Example: Peak current (Ppeak) is 50 A =125%. The peak time is 3 seconds. Nominal load current (Po) is 30 A. 30 A =75% of Inom. According to the diagram, the operating cycle is about 0.45. To = 3 - (0.45 * 3) / 0.45 = 3.6. Maximum repeat time of bonus power is 3.6 seconds.

 

 

Output characteristic

188607_555.eps

Remote control function

188604_555.eps

 

Accessories

Related products

Related

contaclip kds sr90
Product news

Every angle covered with 90 degree cable entry system

Engineers and technicians are seeking solutions that streamline assembly whilst maintaining high levels of protection and flexibility. KDS-SR90 angled screw frames and inlays bring a new level of efficiency to cable routing with a unique 90° entry design.

crouzet millenium slim on limited time discount
Product news

The smallest logic controller ever on limited time discount

The smallest logic controller by Crouzet is now 20% off for a limited time only! A powerhouse packed into just 17.5mm! Efficiency, adaptability, and seamless integration with free software.

11 questions to get the right signalling device with Auer Signal & OEM Automatic
Blog

11 questions to get the right signalling device – a whitepaper

Do you require signalling devices and beacons in your production process? Download our latest whitepaper!

bespoke solutions electricity meter control boxes
Case studies

Control Box Assembly for Industrial Electricity Metering - A case study

Here, our customer requires control boxes for electricity metering systems. We leveraged our expertise to deliver easy-to-install, ready-to-use assemblies. We look forward to creating more of these bespoke control boxes for our customer.

DC circuit protection PISA M and circuit breakers
Blog

Safeguard systems with DC circuit protection

This blog talks all things DC circuit protection including the key components: electronic circuit breakers, fuses and current monitoring devices. As well as how to choose the right protection.

IATECH, the industrial automation technology exhibition OEM automatic
Company news

Recap of IATECH

Did you get a chance to visit IATECH at The Leicester Marriott Hotel? We had over 33 exhibitors and 8 fantastic Tech Talks throughout the day, Read all about the day, here.

Parts Lifetime at 400 V ac, full load and +40 ° C Clamp type Approvals Price
69000 h
Screw on
CB, CE, CSA, GL, UL
93000 h
Screw
CB, CE, CSA, UL

Selected variant

Select a variant in the list

Contact us
If you need any help, you can contact us in one of the following ways:
0116 284 9900
Send e-mail
Use live chat
Do you need help?
Logo

Cookie settings for OEM.CO.UK

Cookies help us improve your experience with us, so in order to be able to handle login information, offer you personalised content and for basic functionality of this website, we use some cookies.

We will never sell on any information about you. 

You can accept all cookies or personalise your cookies preferences, you can also change your cookie preferences at any time by visiting our contact page.

Necessary Cookies

These cookies are necessary for the website to work and can not be turned off in our systems. They are usually used only in response to actions you have taken in connection with a service request, for example when setting personal preferences, logging in or filling out a form.

Analysis and measurement cookies

These cookies allow us to count the number of visits and traffic sources so that we can measure and improve our website performance. They help us know which pages are more or less popular and how visitors navigate around the site. The information that these cookies collect is aggregated and therefore completely anonymous. If you do not allow these cookies, we do not know when you have visited our website.

Marketing cookies

These cookies can be added by our partners. They can use them to create a profile of you, based on your interests, to show you more relevant information. They do not store any personal information - only information about your browser and device. If you do not accept these cookies, you will have a more general and less customized user experience.